USE AND INSTALLATION

This category covers fill, void or cavity materials, which are proprietary materials investigated for use in joint systems, perimeter fire-containment systems, firestop systems, and firestop systems in marine applications. Except as specified below, properties of the fill, void or cavity materials other than the capacity to provide a degree of fire resistance to openings provided in fire-resistive walls, decks, bulkheads or floors have not been investigated.

These materials are intended for installation at a job site in accordance with the application instructions provided with the product and with the instructions specified in the individual joint system, perimeter fire-containment system or firestop system.

The fill, void or cavity material thickness published in the fire-resistance designs is measured wet and may be susceptible to a percentage of shrinkage during the curing process. Firestop systems are investigated after the fill, void or cavity materials are fully cured. Refer to the individual certifications for the investigated percentage of shrinkage.

Authorities Having Jurisdiction should be consulted before installation.

Where indicated in the individual certifications, products covered under this category have also been evaluated by ICC Evaluation Service (ICC-ES).

PRODUCT IDENTITY

The following product identity appears on the product:

    Fill, Void or Cavity Material

RELATED PRODUCTS

See Joint Systems (XHBN), Perimeter Fire-containment Systems (XHDG), Through-penetration Firestop Systems (XHEZ) and Firestop Systems, Marine (XHJN).

ADDITIONAL INFORMATION

For additional information, see Fire-resistance Ratings (BXRH) and Marine Products (AAMP).

REQUIREMENTS

The basic standards used to investigate the systems in which these products are installed are ANSI/UL 1479, "Fire Tests of Penetration Firestops," ANSI/UL 2079, "Tests for Fire Resistance of Building Joint Systems," and ANSI/ASTM E2307, "Standard Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multi-story Test Apparatus."

Where indicated in the individual certifications, fill, void or cavity materials have additionally been investigated to ANSI/ASTM E136, "Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750°C," and/or ASTM C1241, "Standard Test Method for Volume Shrinkage of Latex Sealants During Cure."

The basic standard used to investigate products used as firestop systems in marine applications is the FTP Code, IMO Resolution MSC.307(88), Annex 1, Part 3, "Test for 'A', 'B' and 'F' Class Divisions."

UL MARK

The Certification Mark of UL on the product or on the smallest unit container in which the product is packaged is the only method provided by UL to identify products manufactured under its Certification and Follow-Up Service. The Certification Mark for these products includes the UL symbol, the words "CERTIFIED" and "SAFETY," the geographic identifier(s), and a file number.

Additional Certification Markings

Products covered under this category are additionally marked with the following information:

For fill, void or cavity materials investigated for use in through-penetration firestop systems:

FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS
SEE UL ONLINE CERTIFICATIONS DIRECTORY

For fill, void or cavity materials investigated for use in joint systems:

FOR USE IN JOINT SYSTEMS
SEE UL ONLINE CERTIFICATIONS DIRECTORY

For fill, void or cavity materials investigated for use in perimeter fire-containment systems:

FOR USE IN PERIMETER FIRE-CONTAINMENT SYSTEMS
SEE UL ONLINE CERTIFICATIONS DIRECTORY

For fill, void or cavity materials investigated for use in firestop systems, joint systems and/or perimeter fire-containment systems:

FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS AND/OR
JOINT SYSTEMS AND/OR PERIMETER FIRE-CONTAINMENT SYSTEMS
SEE UL ONLINE CERTIFICATIONS DIRECTORY

Where applicable, the following statement(s) may be added to any of the markings shown above:

ALSO CERTIFIED TO ASTM E136
STANDARD TEST METHOD FOR BEHAVIOR OF MATERIALS
IN A VERTICAL TUBE FURNACE AT 750°C

ALSO CERTIFIED TO ASTM C1241
STANDARD TEST METHOD FOR VOLUME SHRINKAGE
OF LATEX SEALANTS DURING CURE

For fill, void or cavity materials investigated for use in firestop systems in marine applications:

FOR USE IN FIRESTOP SYSTEMS IN MARINE APPLICATIONS
SEE UL ONLINE CERTIFICATIONS DIRECTORY
RATING CLASS DIVISION *

* A-60, A-30, A-15, A-0, B-15, B-0

Alternate UL Mark

The Classification Mark of UL on the product or on the smallest unit container in which the product is packaged is the only method provided by UL to identify products manufactured under its Classification and Follow-Up Service. The Classification Mark for these products includes the UL symbol, the word "CLASSIFIED" above the UL symbol (as illustrated in the Introduction of this Directory), and the following additional information:

For fill, void or cavity materials investigated for use in through-penetration firestop systems:

FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
Control No.

For fill, void or cavity materials investigated for use in joint systems:

FILL, VOID OR CAVITY MATERIAL
FOR USE IN JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
Control No.

For fill, void or cavity materials investigated for use in perimeter fire-containment systems:

FILL, VOID OR CAVITY MATERIAL
FOR USE IN PERIMETER FIRE CONTAINMENT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
Control No.

For fill, void or cavity materials investigated for use in firestop systems, joint systems and/or perimeter fire-containment systems:

FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS AND/OR
JOINT SYSTEMS AND/OR PERIMETER FIRE CONTAINMENT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
Control No.

Where applicable, the following statement(s) may be added to any of the Classification Marks shown above:

ALSO CLASSIFIED IN ACCORDANCE WITH ASTM E136
STANDARD TEST METHOD FOR BEHAVIOR OF MATERIALS
IN A VERTICAL TUBE FURNACE AT 750°C

 

ALSO CLASSIFIED IN ACCORDANCE WITH ASTM C1241
STANDARD TEST METHOD FOR VOLUME SHRINKAGE
OF LATEX SEALANTS DURING CURE

For fill, void or cavity materials investigated for use in firestop systems in marine applications:

FILL, VOID OR CAVITY MATERIAL
FOR USE IN FIRESTOP SYSTEMS IN MARINE APPLICATIONS
SEE UL FIRE RESISTANCE DIRECTORY
RATING CLASS DIVISION *
Control No.

* A-60, A-30, A-15, A-0, B-15, B-0

* * * * * * * * * * * * * * * * * * * * * * * * *

UL, in performing its functions in accordance with its objectives, does not assume or undertake to discharge any responsibility of the manufacturer or any other party. UL shall not incur any obligation or liability for any loss, expense or damages, including incidental or consequential damages, arising out of or in connection with the use, interpretation of, or reliance upon this Guide Information.

Firestopping
Last Updated on 2016-08-11
XHHW.GuideInfo XHHW Active 20160811 20160815

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2019 UL LLC".