THROUGH-PENETRATION FIRESTOP SYSTEM

Assembly Usage Disclaimer

XHEZ - Through-penetration Firestop Systems


See General Information for Through-penetration Firestop Systems

System No. W-L-7203

June 02, 2011

F Ratings — 1 and 2 Hr (See Item 1)

T Ratings — 1 and 2 Hr (See Item 1)

    1. Wall Assembly — The 1 or 2 hr fire rated framed gypsum board wall assembly shall be constructed of the materials and in the manner specified in the individual U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
      A. Studs — Wall framing shall consist of steel channel studs. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
      B. Gypsum Board* — The gypsum board type, thickness, number of layers and orientation shall be, as specified in the individual Wall and Partition Design. Size of cutout made to accommodate steel box (Item 3) is to be 1/4 in. (6 mm) wider and 1/4 in. (6 mm) higher than the width and height of the steel box.

      The hourly F and T Ratings are equal to the hourly rating of the wall assembly.

    2. Insulation — The spaces between the sides of the steel box and the studs, the space between the back of the box and the gypsum board and the stud cavities above, below and on each side of the steel box are to be tightly packed with min R19 glass fiber batt insulation or mineral wool insulation to the full depth of the stud cavity.
    3. Steel Box — Min 16 gauge, max 24 in. (610 mm) wide by max 24 in. (610 mm) high by max 4 in. (102 mm) deep recessed steel utility box with screw cover or hinged steel door installed through one side of wall only. Steel box secured to steel studs with steel screws. Bottom and/or top of steel box may be penetrated by up to five nom 1 in. (25 mm) diam steel EMT conduits and up to four nom 3/4 (19 mm) steel EMT conduits. Open conduits which terminate within the box shall be sealed with caulk (Item 5) or plugged with a ball of putty (Item 6).
    4. Fill, Void or Cavity Materials* — Nom 1/16 in. (2 mm) thick intumescent material supplied in 1, 6 and 12 in. (25, 152 and 305 mm) wide strips. Min one layer of intumescent material applied to inside perimeter of box (item 3) closest to cover or door. Two 12 in. (305 mm) wide strips cut to the width of the box to completely cover the interior surface of the box cover. Two 6 in. (152 mm) wide cut to the width of the box to cover the top and bottom of the interior back panel of the box.

    RECTORSEAL — Metacaulk Joint Strip, Biostop Joint Strip, FlameSafe Joint Strip.


    5. Fill, Void or Cavity Materials* - Caulk or Sealant — (Not Shown) - Nom 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with surface of wall. Nom 1/4 in. (6 mm) in diam bead of caulk applied to the point contact locations at the box/gypsum interface. The end of each open pipe or tube which terminates within the box shall be sealed with a min 1/2 in. (13 mm) depth of caulk.

    RECTORSEAL — Metacaulk 1000, Biostop 500+, FlameSafe 1900


    6. Fill, Void or Cavity Materials* - Putty — (Not Shown) - As an alternate to the caulk (Item 5), the end of each conduit which terminates within the box may be sealed with a min 1/2 in. (13 mm) depth of putty fill material.

    RECTORSEAL — Metacaulk Fire Rated Putty, Biostop Fire Rated Putty


    * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

Last Updated on 2011-06-02
XHEZ.W-L-7203 W-L-7203 XHEZ 613495002 SYSTEM Active 20110602 20110602 613495002 613495002 613495002

Design/System/Construction/Assembly Usage Disclaimer

  • Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Certified products, equipment, system, devices, and materials.
  • Authorities Having Jurisdiction should be consulted before construction.
  • Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field.
  • When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction.
  • Only products which bear UL's Mark are considered Certified.

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2019 UL LLC".