GENERAL

This category covers fluid handling systems consisting of pumps, electric motors, frequency drives, control valves, gauges and piping mounted on a structural steel base. They are used for plumbing boosters, heat transfer, hot water heating, HVAC chilled and hot water packages, irrigation, boiler feed and condensate packages, and similar applications.

This category also covers fountain pumping systems intended for connection to permanently installed architectural and floating fountains. They are intended for installation in accordance with Article 680 or 682 of ANSI/NFPA 70, "National Electrical Code" (NEC). If provided with a control panel, its nameplate includes "Industrial Control Panel for Floating Fountain,""Industrial Control Panel for Permanently Installed Fountain" or "Fountain Control Panel."

RATINGS

Packaged pumping systems are rated 600 V or less. The supply input is rated in full load amperes, voltage, number of phases, frequency, and the rating of the largest motor load.

The system and components of the system are intended to be used within the rated working pressure and with the appropriate liquids in accordance with system markings.

SPECIAL CONSIDERATIONS

These pumping systems have not been investigated for the handling of hazardous materials or for use in hazardous (classified) locations as defined in the NEC.

LIMITED-PRODUCTION EQUIPMENT

This category also covers single pieces of equipment or equipment manufactured in a limited quantity under a single production run in accordance with UL's Limited Production Certification Program. This limited-production equipment meets all of the same requirements as equipment that may be produced under continuous production runs, except there is no ongoing surveillance (UL Follow-Up Service), since subsequent UL-certified production does not continue after the single run. UL certification is based on the serial number or other discrete identifier of the limited-production equipment, and not based on any model number. A UL Certificate of Compliance is also issued (see UL CERTIFICATE below).

PRODUCT IDENTITY

One of the following product identities appears on the product:

    Packaged Fountain Pumping System

    Packaged Pumping System

RELATED PRODUCTS

Systems covered under this category may also be covered under Drinking Water System Components (FDNP). The investigation of drinking water system components is conducted with respect to contaminants that can be introduced into the drinking water supply from their base metal alloy, plastic resin, or other nonmetallic parts such as gaskets, seals, coatings, adhesives, filter media, cement linings or the like.

Systems investigated together with air conditioning and refrigeration equipment are covered under Heating and Cooling Equipment (LZFE) or Specialty Refrigeration Equipment (SROT).

Pumping equipment intended for fire service is covered under Fire Pump Motors (QXZF).

Pumps intended for use with combustible or flammable liquids, corrosive liquids, or aqueous solutions containing corrosive materials are covered under Power-operated Pumps (RBOG), or Pumps, Power Operated, Flammable Liquid (RCRX).

Prepackaged combinations of components, such as pumps, filters, heaters, blowers, lights and controls, intended for use with field-supplied hot tubs or spas are covered under Hot Tub and Spa Equipment Assemblies (WBYQ).

Pumps investigated for use with or in proximity to swimming pools or spas are covered under Pumps (WCSX).

ADDITIONAL INFORMATION

For additional information, see Electrical Equipment for Use in Ordinary Locations (AALZ) and Plumbing and Associated Products (AAPP).

REQUIREMENTS

The basic standards used to investigate products in this category are ANSI/UL 508, "Industrial Control Equipment," ANSI/UL 778, "Motor-Operated Water Pumps," and UL 508A, "Industrial Control Panels."

The basic standard used to investigate packaged pumping systems for heating and cooling equipment in this category is ANSI/UL 1995, "Heating and Cooling Equipment."

UL MARK

The Certification Mark of UL on the product is the only method provided by UL to identify products manufactured under its Certification and Follow-Up Service. The Certification Mark for these products includes the UL symbol, the words "CERTIFIED" and "SAFETY," the geographic identifier(s), and a file number.

The Certification Mark covers only the equipment mounted to the common structural frame.

Alternate UL Mark

The Listing Mark of UL on the product is the only method provided by UL to identify products manufactured under its Listing and Follow-Up Service. The Listing Mark for these products includes the UL symbol (as illustrated in the Introduction of this Directory) together with the word "LISTED," a control number, and the product name "Packaged Pumping System" or "Packaged Fountain Pumping System."

The Listing Mark covers only the equipment mounted to the common structural frame.

UL CERTIFICATE

A UL Certificate of Compliance is issued for limited-production equipment investigated under UL's Limited Production Certification Program. Issuance of a UL Certificate of Compliance indicates that UL has investigated a sample of the equipment and determined that it complies with the applicable requirements of this category. Each Certificate of Compliance is valid only for the individual units covered by the investigation and certification by UL.

At a minimum, each Certificate contains the following information:

  • Certificate number
  • Certificate issue date
  • Report reference
  • Responsible company name and address
  • Limited-production equipment serial number/discrete identifier
  • Applicable standards

* * * * * * * * * * * * * * * * * * * * * * * * *

UL, in performing its functions in accordance with its objectives, does not assume or undertake to discharge any responsibility of the manufacturer or any other party. UL shall not incur any obligation or liability for any loss, expense or damages, including incidental or consequential damages, arising out of or in connection with the use, interpretation of, or reliance upon this Guide Information.

Packaged Fountain Pumping SystemsPumping Systems, PackagedPumping Systems, Packaged, FountainSkid PacksSkid Pumps
Last Updated on 2018-11-19
QCZJ.GuideInfo QCZJ Active 20181119 20181119

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2019 UL LLC".