UL PRODUCT CATEGORY

[Fire Doors] Access-type Fire Doors, GSOT


See General Information for Fire Doors

712.3.2712.4.1.5715.4716.4

USE AND INSTALLATION

This category covers access-type fire doors, which are assemblies consisting of single-swinging steel doors with frames, self-latching devices and closing mechanisms.

Access-type fire door assemblies are intended to be installed vertically in concrete and masonry walls unless otherwise noted in the individual certifications. Access-type fire door assemblies intended to be installed in nonmasonry walls or in the ceiling of fire-resistive horizontal assemblies should be installed in accordance with the installation instructions provided with each assembly.

Access-type fire door assemblies are intended to be installed in accordance with ANSI/NFPA 80, "Fire Doors and Other Opening Protectives."

Authorities Having Jurisdiction should be consulted before installation.

PRODUCT IDENTITY

The following product identity appears on the product:

    Access Frame and Fire Door Assembly

RELATED PRODUCTS

See Floor Access Doors (CCJV).

ADDITIONAL INFORMATION

For additional information, see Fire Doors (GSNV) and Fire-resistance Ratings (BXRH).

REQUIREMENTS

The basic standard used to investigate products in this category when installed in walls is ANSI/UL 10B, "Fire Tests of Door Assemblies."

The basic standard used to investigate products in this category when installed in ceilings of horizontal fire-resistive assemblies is ANSI/UL 263, "Fire Tests of Building Construction and Materials."

UL MARK

The Certification Mark of UL on the product is the only method provided by UL to identify products manufactured under its Certification and Follow-Up Service. The Certification Mark for these products includes the UL symbol, the words "CERTIFIED" and "SAFETY," the geographic identifier(s), and a file number.

The Certification Mark covers the design and construction of the door, frame and hardware.

Additional Certification Markings

Products covered under this category are additionally marked with the following information:

AS TO FIRE RESISTANCE
RATING: + H
TEMP RISE: ++
+ 4, 3, 1-1/2 or 3/4


++ 30 MIN - 250°F MAX, 30 MIN - 450°F MAX, 30 MIN - 650°F MAX, or no reference to temperature rise when the temperature rise exceeds 650°F at 30 min.

Alternate UL Mark

The Classification Mark of UL on the product is the only method provided by UL to identify products manufactured under its Classification and Follow-Up Service. The Classification Mark covers the design and construction of the door, frame and hardware. The Classification Mark for these products includes the UL symbol, the word "CLASSIFIED" above the UL symbol (as illustrated in the Introduction of this Directory), and the following additional information:

ACCESS FRAME AND FIRE DOOR ASSEMBLY
FIRE RESISTANCE CLASSIFICATION
RATING: + HR
TEMP RISE: ++
No.

+ 4, 3, 1-1/2 or 3/4

++ 30 MIN - 250°F MAX, 30 MIN - 450°F MAX, 30 MIN - 650°F MAX, or no reference to temperature rise when the temperature rise exceeds 650°F at 30 min.

* * * * * * * * * * * * * * * * * * * * * * * * *

UL, in performing its functions in accordance with its objectives, does not assume or undertake to discharge any responsibility of the manufacturer or any other party. UL shall not incur any obligation or liability for any loss, expense or damages, including incidental or consequential damages, arising out of or in connection with the use, interpretation of, or reliance upon this Guide Information.

Access Frame and Fire Door AssembliesFire Doors, Access Type
Last Updated on 2013-05-16
GSOT.GuideInfo GSOT Active 20130516 20080522

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2019 UL LLC".