Design No. U648

July 25, 2018

Nonbearing Wall Rating — 3 HR.

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

    (For Fire Exposure to Both Sides Except As Noted in Item 4 and 6).
    1. Steel Supports — 3 by 3 by 1/4 in. steel, attached to masonry with expansion shields and 3/8 by 2-1/8 in. steel bolts spaced 18 in. OC.
    2. Flashing Angle — 2 by 3 in. 18 MSG metal coated steel, 2 in. leg attached to masonry with No. 12 by 1-1/2 in. long self-tapping hex washer head screws in 1-1/2 in. long split steel inserts spaced 18 in. OC.
    3. Wall and Partition Facings and Accessories* — Steel Liners — min 18 MSG, 12 and 24 in. wide steel liners forming the interior side of the wall, attached to top and bottom support angles with No. 12 by 3/4 in. long hex-head self-tapping steel screws spaced 12 in. OC max. The side wall flashing is attached to the liner with 1/8 in. diameter stainless steel pop rivets or No. 12 by 3/4 in. long self-tapping hex washer head steel screws spaced 12 in. OC. Adjacent liners fastened through lips with No. 12 by 3/4 in. long self-tapping screws spaced 4 ft OC. maximum vertically.

    CENTRIA, A DIVISION OF NCI GROUP, INC — Types C-Panel, CFP III, L1 Liner, L1-2 Liner, L2 Liner, L2-2 Liner, Channelwall I, L2-3 Liner, Trimwall, Varispan, L-10, L-10P, L-11, L-11P, L-20, L-20P, L-21, L-21P, L-36, L-36P, L-41, L-41P


    METAL SALES MANUFACTURING CORPORATION — Types TL-19A, TL-19B, TL-20, TL-21, TL-17, TL-18


    MORIN CORP — Types L-12W, L-12W-1, L-24W, L-24W-2, L2-16, L3-16, L2-24, L3-24


    3A. Wall and Partition Facings and Accessories* — Steel Liners — As an alternate to Item 3, No. 20 MSG min steel liners attached to support angles with No. 14 by 1 in. long hex head, self-tapping steel screws, one per panel.

    CENTRIA, A DIVISION OF NCI GROUP, INC — Types IW11A, L-21


    4. Batts and Blankets* — (optional if exposed on interior (liner) face only) — 1-1/2 in. thick glass fiber or mineral wool batts, placed in liner cavity with horizontal joints staggered in adjacent cavities.

    Any glass fiber or mineral wool batt material bearing the UL Classification Marking as to Fire Resistance.

    See Batts and Blankets* (BZJZ) category for names of Classified companies.

    4A. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 4) — (100% Borate Formulation) — Spray applied cellulose material. The fiber is applied with water to completely fill the enclosed cavity in accordance with the application instructions supplied with the product with a nominal dry density of 2.7 lb/ft3. Alternate Application Method: The fiber is applied without water or adhesive at a nominal dry density of 3.5 lb/ft3, in accordance with the application instructions supplied with the product.

    U S GREENFIBER L L C — INS735 & INS745 for use with wet or dry application. INS765LD and INS770LD are to be used for dry application only.


    4B. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 4) - Spray applied cellulose fiber. The fiber is applied with water to completely fill the enclosed cavity in accordance with the application instructions supplied with the product. The minimum dry density shall be 4.30 lbs/ft3.

    INTERNATIONAL CELLULOSE CORP — Celbar-RL


    5. Sub-girts — Hat shaped, min channel. 1/2 in. deep by 3-1/2 wide with min 5/8 in. wide legs, 18 MSG galv steel attached to lip of liner with one No. 12 — 3/4 in. long hex washer head, self-tapping steel screw located alternately along the upper and lower legs. Maximum sub-girt spacing is 48 in. OC. vertically with top and bottom sub-girts located not more than 3 in. from supporting angles.
    6. Gypsum Board* — (Any Gypsum Board bearing the UL Classification Marking as to Fire Resistance) — (Four layers) 5/8 in. thick by 48 in. wide sheets applied vertically. Vertical and horizontal joints between adjacent layers staggered. First and second layer attached to sub-girts with No. 6 - 1-5/8 in. long self-drilling self-tapping Phillips bugle head screws located alternately 10 in. from vertical edges in each sheet for first layer and 9 in. from vertical edges in each sheet for second layer. Third layer attached to first and second with No. 10 - 1-1/2 in. long double lead bugle head screws spaced vertically 24 in. OC. and 12 in. from edges. Fourth layer attached to third and second layer with double lead bugle head screws spaced vertically 24 in. OC and 9 in. from the edges.

    Any UL Classified Gypsum Board that is eligible for use in Design Nos. L501, G512 or U305. See Gypsum Board (CKNX) category for names of Classified companies.

    6A. Gypsum Board* — (As an alternate to Item 6) — Nominal 5/8 in. thick, 4 ft wide panels, secured as described in Item 6.

    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM — Type QuietRock ES


    6B. Wall and Partition Facings and Accessories* — (As an alternate to Items 6 and 6A) — Composite Gypsum Panel — Nominal 5/8 in. thick, 4 ft wide panels, secured as described in Item 6.

    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM — Type QuietRock 527


    7. Sub-girts — Hat shaped, min 1/2 in. deep by 3-1/2 in. wide with min 5/8 in. wide legs, 18 msg galv steel placed over wall board and attached through the wall board to the first set of sub-girts with No. 12-14 by 3-1/2 in. long self drilling self-tapping hex head steel screws spaced at 24 in. OC along sub-girt.
    8. Wall and Partition Facing Units and Accessories* — Steel Facing Units — Min 24 MSG of various shapes supplied in 12, 30 and 36 in. widths, attached to sub-girt with one No. 14-3/4 in. long hex washer head self-tapping or No. 12-1 in. long hex washer head self-drilling, self-tapping steel screw at each joint. For units exceeding 12 in. in width, additional screws are necessary to allow a maximum screw spacing of 14.4 in. OC along sub-girts. Exposed fasteners require a steel and neoprene sealing washers. Vertical joints are stitched at 24 in. OC with No. 12-3/4 in. long self-tapping screws. Flashing angle attached to face panel with 1/8 in. diameter stainless steel pop rivets or No. 12-3/4 in. long hex washer head self-tapping screws at 12 in. OC vertically.

    CENTRIA, A DIVISION OF NCI GROUP, INC — Types BR Deck, Channelwall I, Channelwall IV, Channelwall VI, Contour wall, Dyna-Span, Featurewall, N-Wall, Shadowall, Style Rib, Trimwall, V-Line Rib, Wedgewall, 1/2 in. Econolap, 3/4 in. Econolap, 4 in. Rib, 8 in. Ribline, Box Rib, CFP II, CFP III, Hi Rib, HR-35, Modified V Beam, Style Rib, Super Rib, V Beam,, IW10A, IW11A, IW13A, IW18A, IW20A, IW21A, IW30A, IW31A, IW40A, IW41A, Section 3, 12 or 30, C15-40, HR5-36, BR5-36, MR3-36, LR4-36, TR4-36, Corrugated, Strudi-Rib, Huski-Rib, Box-Rib, Magna-Rib, SR3-36, IW14A, IW60A or CS-200, CS-200E, CS-210, CS-210E, CS-220, CS-220E, CS-260, CS-260E, CS-610, CS-610E, CS-620, CS-620E, CS-630, CS-630E, CS-660, CS-660E, CC-260, CC-262, CC-263, CC-624, CC-662, CC-663, CC-664.


    METAL SALES MANUFACTURING CORPORATION — Types T-2, T-3, T-4, T-5, T-6, T-6A, T-7, T-7A, T-8, T-8 Modified, T-9, T-11, T-12, T-10A, T-10B, T-10C, T-10D, T-10E, TL17, TL-17A, TL-17B, TL-17C, TL-17D, TL-18, TL-1222, TL-1251, TDR-6, TDR-9, TDR-12, T-13, T-14, T-15, T-23, T-24, T-25, T-26, B-Type, and B-Type Modified.


    MORIN CORP — Types BR7-35-PROFILE A, BR9-36-PROFILE A, BR-28-PROFILE A, BR-28-PROFILE B, C-37-PROFILE A ,C-40-PROFILE A, E-36-PROFILE A, E8-40-PROFILE A, F-12-0, F-12-1, F-12-2, F-24-0, F-24-5, L2-16, L2-24, L-24W-0/L-24-0, L3-16, L3-24, MR-36-PROFILE A, MR-36-PROFILE B, MX 1.0 PREVIOUSLY U-12, N-12-0, N-12-2, 0.24W-PROFILE A, T-12-3, VB-36-PROFILE A, W-12, Y-36-PROFILE A, Y-36-PROFILE B.


    8A. Wall and Partition Facings and Accessories* — Steel Face Panels — As an alternate to Item 8, No. 20 MSG min, steel facing units. (For rating applicable when exposed to liner side only, No. 24 MSG min.) Fastened to sub-girts with No. 14 by 3/4 in. long, hex-head, self-tapping, self-drilling screws.

    CENTRIA, A DIVISION OF NCI GROUP, INC — Types HR5-36, IW11A, IW21A.


    * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

Last Updated on 2018-07-25
BXUV.U648 U648 BXUV 997005001 DESIGN Active 20180725 20180725 128669004 997005001 707669001 128669004 184866001 979414001 100046076 100046076 128669004 997005001 128669004

Design/System/Construction/Assembly Usage Disclaimer

  • Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Certified products, equipment, system, devices, and materials.
  • Authorities Having Jurisdiction should be consulted before construction.
  • Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field.
  • When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction.
  • Only products which bear UL's Mark are considered Certified.

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2019 UL LLC".