Design No. U502

April 16, 2019

Nonbearing Wall Rating — 2 Hr

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

    1. Wood+ or Steel Runner — 1 1/2X1 5/8-in. yellow pine, or 24 MSG galv steel channels used on sill, lintel, and sides, fastened to concrete or masonry with 1/4-in. bolts and expansion shields or 3 1/2-in. masonry nails, spaced 16 to 20 in. OC.
    2. Nails or Screws — Used to secure inner layer of wallboard to wood or steel runners. Nails, 5d, 1 5/8 in. long, 1/4 -in. heads, spaced 8 in. OC are used with wood runners. Sheet metal screws, No. 10 or larger, spaced 12 in. OC are used with metal runners, 8d, 2 1/2 in. long, 1/4-in. diam head nails spaced 8 in. OC to secure outer layer of wallboard to wood runners, or No. 10 screws spaced 12 in. OC used with metal runners.
    3. Gypsum Board* Ribs — 2 layers of min. 1/2 in. thick wallboard glued together with casein type glue to form 6 in. wide ribs, 4 in. less in length than partition height. Located at vertical joints and spaced 24 in. OC, staggered 12 in. from ribs of opposite side.

    ACADIA DRYWALL SUPPLIES LTDType X, 5/8 Type X, Type Blueglass Exterior Sheathing


    AMERICAN GYPSUM CO Type AG-C.


    CERTAINTEED GYPSUM INCType SF3, EGRG, GlasRoc, GlasRoc-2, Type X, Type X-1, Easi-Lite Type X-2, Type C.


    CONTINENTAL BUILDING PRODUCTS OPERATING CO, L L CTypes LGFC-C/A, LGFC-WD, LGLLX, CLLX.


    GEORGIA-PACIFIC GYPSUM L L CTypes 5, 6, DAPC, GPFS1, LS, Type X, Veneer Plaster Base - Type X, Water Rated - Type X, Sheathing - Type X, Soffit - Type X, Type TG-C, GreenGlass Type X, Type X ComfortGuard Sound Deadening Gypsum Board, Type LWX, Veneer Plaster Base-Type LWX, Water Rated-Type LWX, Sheathing Type-LWX, Soffit-Type LWX, Type DGLW, Water Rated-Type DGLW, Sheathing Type- DGLW, Soffit-Type DGLW, Type LW2X, Veneer Plaster Base - Type LW2X, Water Rated - Type LW2X, Sheathing - Type LW2X, Soffit - Type LW2X, Type DGL2W, Water Rated - Type DGL2W, Sheathing - Type DGL2W.


    NATIONAL GYPSUM COTypes eXP-C, FSK, FSK-C, FSK-G, FSMR-C, FSW, FSW-3, FSW-8, FSW-C, FSW-G, FSMR-C.


    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUMTypes PG-3, PG-11, PGS-WRS.


    SAINT-GOBAIN GYPROC MIDDLE EAST FZEType Gyproc FireStop, Gyproc FireStop MR, Gyproc FireStop M2TECH, Gyproc FireStop ACTIV'Air, Gyproc FireStop MR ACTIV'Air, Gyproc FireStop M2TECH ACTIV'Air


    THAI GYPSUM PRODUCTS PCLType X, Type C.


    3A. Gypsum Board* Ribs — 2 layers of 5/8 in. thick panels glued together with casein type glue to form 6 in. wide ribs, 4 in. less in length than partition height. Located at vertical joints and spaced 24 in. OC, staggered 12 in. from ribs of opposite side.

    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUMType QuietRock ES.


    3B. Wall and Partition Facings and Accessories* Ribs — 2 layers of 5/8 in. thick panels glued together with casein type glue to form 6 in. wide ribs, 4 in. less in length than partition height. Located at vertical joints and spaced 24 in. OC, staggered 12 in. from ribs of opposite side.

    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUMType QuietRock QR-527.


    4. Gypsum Board* — 5/8 in. thick, inner layer, with vertical joints, attached to ribs with glue and screws and to runners with nails or sheet metal screws. Outer layer, with horizontal joints, attached to inner layer with glue, nails, and screws.

    ACADIA DRYWALL SUPPLIES LTDType X, 5/8 Type X, Type Blueglass Exterior Sheathing


    AMERICAN GYPSUM COTypes AGX-1, M-Glass, AG-C, LightRoc.


    BEIJING NEW BUILDING MATERIALS PUBLIC LTD CO Type DBX-1.


    CERTAINTEED GYPSUM INC Type FRPC, SF3, Type X, Type X-1, Easi-Lite Type X-2, Type C, ,SilentFX or 5/8" Easi-Lite Type X.


    CONTINENTAL BUILDING PRODUCTS OPERATING CO, L L CTypes LGFC2A, LGFC6A, LGFC-C/A.


    GEORGIA-PACIFIC GYPSUM L L CTypes 5, 6, 9, C, DA, DAP, DAPC, DGG, DS, GPFS1, GPFS6, LS, TG-C, GreenGlass Type X, Type X ComfortGuard Sound Deadening Gypsum Board Type LWX, Veneer Plaster Base-Type LWX, Water Rated-Type LWX, Sheathing Type-LWX, Soffit-Type LWX, Type DGLW, Water Rated-Type DGLW, Sheathing Type- DGLW, Soffit-Type DGLW, Type LW2X, Veneer Plaster Base - Type LW2X, Water Rated - Type LW2X, Sheathing - Type LW2X, Soffit - Type LW2X, Type DGL2W, Water Rated - Type DGL2W, Sheathing - Type DGL2W.


    NATIONAL GYPSUM COTypes eXP-C, FSK-1, FSK-C, FSK-G, FSW-1, FSW-C, FSW-G, FSW-6, FSL.


    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUMTypes C, PG-3, PG-4, PG-6, PG-9, PG-11, PG-C, PGS-WRS.


    SAINT-GOBAIN GYPROC MIDDLE EAST FZEType Gyproc FireStop, Gyproc FireStop MR, Gyproc FireStop M2TECH, Gyproc FireStop ACTIV'Air, Gyproc FireStop MR ACTIV'Air, Gyproc FireStop M2TECH ACTIV'Air, Gyproc DuraLine, Gyproc DuraLine MR, Gyproc DuraLine M2TECH, Gyproc DuraLine ACTIV'Air, Gyproc DuraLine MR ACTIV'Air, Gyproc DuraLine M2TECH ACTIV'Air


    SIAM GYPSUM INDUSTRY (SARABURI) CO LTDType EX-1


    THAI GYPSUM PRODUCTS PCLType X or Type C


    4A. Gypsum Board* — (As an alternate to Item 4) — Nominal 5/8 in. thick, 4 ft wide panels, applied vertically only and secured as described in Item 4.

    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUMType QuietRock ES.


    4B. Wall and Partition Facings and Accessories* — (As an alternate to Item 4 and 4A) — Nominal 5/8 in. thick, 4 ft wide panels, applied vertically only and secured as described in Item 4.

    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUMType QuietRock QR-527.


    5. Adhesive — Casein type, mixed 4 lbs of dry powder to 1.4 gal of water.
    6. Screws — No. 8 Phillips head screws. 1-1/2 in. long attaching inner layer to ribs spaced vertically 20 in. OC, 2 in. long attaching outer layer to ribs spaced vertically and horizontally 24 in. OC along edges of boards at the joints.
    7. Nails — 8d, 2-1/2 in. long finishing nails spaced vertically 8 in. OC and at 45 degree angle attaching outer layer through inner layer to ribs.
    8. Finishing System — Exposed or covered with fiber tape and joint finisher. As an alternate, nominal 3/32 in. thick gypsum veneer plaster may be applied to the entire surface of Classified veneer baseboard. Joints reinforced.

    +When wood runners are used the rating is combustible.

    * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

Last Updated on 2019-04-16
BXUV.U502 U502 BXUV 100046076 DESIGN Active 20190416 20190416 100562937 283066001 100219806 294450001 299592001 923830002 100046076 100572141 100584219 100046076 100046076 100562937 283066001 736720001 100219806 294450001 299592001 923830002 100046076 100572141 798029001 100584219 100046076 100046076

Design/System/Construction/Assembly Usage Disclaimer

  • Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Certified products, equipment, system, devices, and materials.
  • Authorities Having Jurisdiction should be consulted before construction.
  • Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field.
  • When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction.
  • Only products which bear UL's Mark are considered Certified.

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2019 UL LLC".