Design No. U471

January 24, 2018

Nonbearing Wall Rating — 1-1/2 HR.

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

    1. Studs — Channel-shaped, min 3-5/8 in. wide with 1-1/4 in. flanges and 3/8 in. lips. Fabricated from No. 25 MSG galv steel. Max stud spacing is 24 in. OC. Stud length cut 3/4 in. less than assembly height.
    1A. Framing Members* — Steel Studs — Not Shown — In lieu of Item 1 — For use with Item 2A, proprietary channel shaped steel studs, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel. Studs cut 3/4 in. less in length than assembly height. Max stud spacing is 24 in. OC.

    CALIFORNIA EXPANDED METAL PRODUCTS COViper20™


    MARINO/WARE, DIV OF WARE INDUSTRIES INCViper20™


    FUSION BUILDING PRODUCTSViper20™


    IMPERIAL MANUFACTURING GROUP INCViper20™


    1B. Framing Members* — Steel Studs — Not Shown — In lieu of Item 1 — For use with Item 2B, channel shaped steel studs, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel. Studs cut 3/4 in. less in length than assembly height. Max stud spacing is 24 in. OC.

    CLARKDIETRICH BUILDING SYSTEMSCD ProSTUD


    DMFCWBS L L CProSTUD


    MBA METAL FRAMINGProSTUD


    RAM SALES L L CRam ProTRAK


    STEEL STRUCTURAL PRODUCTS L L CTri-S ProSTUD


    1C. Framing Members* — Steel Studs — Not Shown — In lieu of Item 1 — For use with Item 2C, proprietary channel shaped steel studs, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel. Studs cut 3/4 in. less in length than assembly height. Max stud spacing is 24 in. OC.

    TELLING INDUSTRIES L L CViper20™


    1D. Framing Members* — Steel Studs — Not Shown — In lieu of Item 1 — For use with Item 2D, channel shaped steel studs, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel. Studs cut 3/4 in. less in length than assembly height. Max stud spacing is 24 in. OC.

    TELLING INDUSTRIES L L CTRUE-STUD™


    1E. Framing Members* — Steel Studs — As an alternate to Item 1 — For use with Item 2A (3-5/8 in. wide track), channel shaped studs, fabricated from min 25 MSG corrosion-protected steel, 1-1/4 in. wide by 3-5/8 in. deep, spaced a max of 24 in. OC. Studs to be cut 3/8 to 3/4 in. less than assembly height.

    MARINO/WARE, DIV OF WARE INDUSTRIES INCStudRite™


    1F. Framing Members* — Steel Studs — Not Shown — In lieu of Item 1 — For use with Item 2E, channel shaped steel studs, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel. Studs cut 3/4 in. less in length than assembly height. Max stud spacing is 24 in. OC.

    STEEL INVESTMENT GROUP L L CAlphaSTUD


    2. Floor and Ceiling Runners — Channel-shaped, min 3-5/8 in. wide with 1-1/8 in. flanges, fabricated from No. 25 MSG galv steel. Attached to floor and ceiling with runners fasteners 24 in. OC, max.
    2A. Framing Members* — Floor and Ceiling Runner — Not Shown — In lieu of Item 2 — For use with Item 1A, proprietary channel shaped runners, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max.

    CALIFORNIA EXPANDED METAL PRODUCTS COViper20™ Track


    MARINO/WARE, DIV OF WARE INDUSTRIES INCViper20™ Track


    FUSION BUILDING PRODUCTSViper20™ Track


    IMPERIAL MANUFACTURING GROUP INCViper20™ Track


    2B. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Item 2 — For use with Item 1B, channel shaped runners, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max.

    CLARKDIETRICH BUILDING SYSTEMSCD ProTRAK


    DMFCWBS L L CProTRAK


    MBA METAL FRAMINGProTRAK


    RAM SALES L L CRam ProSTUD


    STEEL STRUCTURAL PRODUCTS L L CTri-S ProTRAK


    2C. Framing Members* — Floor and Ceiling Runner — Not Shown — In lieu of Item 2 — For use with Item 1C, proprietary channel shaped runners, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max.

    TELLING INDUSTRIES L L CViper20™ Track


    2D. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Item 2 — For use with Item 1D, channel shaped runners, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max.

    TELLING INDUSTRIES L L CTRUE-TRACK™


    2E. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Item 2 — For use with Item 1F, channel shaped runners, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max.

    STEEL INVESTMENT GROUP L L CAlphaTRAK


    3. Mineral and Fiber Boards* — 0.591 in. (15 mm) thick, square edge boards. Board joints centered on studs. Attached to studs and floor and ceiling runners with screws, (Item 4). Max spacing of screws along the board perimeter and in the field is 12 in. OC. Screws along joints spaced 5/16 in. to 3/8 in. from the joint and staggered a min of 1-3/4 in. from the screws on the opposite side of the joints.

    PROMAT UK LTDPROMAT-H.


    4. Fasteners — Type S, bugle-head steel screws, self-drilling and self-tapping, 1-5/8 in. long.
    5. Batts and Blankets* — Min 3-1/4 in. thick mineral wool batt insulation, nom 4 pcf density.

      See Batts and Blankets (BZJZ) category for names of manufacturers.

    5A. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 5) — (100% Borate Formulation) — Spray applied cellulose material. The fiber is applied with water to completely fill the enclosed cavity in accordance with the application instructions supplied with the product with a nominal dry density of 2.7 lb/ft3. Alternate Application Method: The fiber is applied without water or adhesive at a nominal dry density of 3.5 lb/ft3, in accordance with the application instructions supplied with the product.

    U S GREENFIBER L L CINS735 & INS745 for use with wet or dry application. INS765LD and INS770LD are to be used for dry application only.


    5B. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 5) — Spray applied cellulose fiber. The fiber is applied with water to completely fill the enclosed cavity in accordance with the application instructions supplied with the product. The minimum dry density shall be 4.30 lbs/ft3.

    INTERNATIONAL CELLULOSE CORPCelbar-RL


    * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

Last Updated on 2018-01-24
BXUV.U471 U471 BXUV 725188001 DESIGN Active 20180124 20180125 100039004 980447001 P1823606 100567625 100570268 100530754 100557430 100593062 100581840 100512119 100512119 980447001 P1662204 100039004 980447001 P1823606 100567625 100570268 100530754 100557430 100593062 100581840 100512119 100512119 P1662204 725188001 184866001 979414001

Design/System/Construction/Assembly Usage Disclaimer

  • Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Certified products, equipment, system, devices, and materials.
  • Authorities Having Jurisdiction should be consulted before construction.
  • Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field.
  • When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction.
  • Only products which bear UL's Mark are considered Certified.

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2019 UL LLC".