FIRE-RESISTANCE DESIGN

Assembly Usage Disclaimer

BXUV - Fire Resistance Ratings - ANSI/UL 263

BXUV7 - Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada

See General Information for Fire-resistance Ratings - ANSI/UL 263

See General Information for Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada

Design No. M519

November 17, 2017

Unrestrained Assembly Rating - 1 Hr.

Finish Rating - 22 minutes

This design was evaluated using a load design method other than the Limit States Design Method (e.g., Working Stress Design Method). For jurisdictions employing the Limit States Design Method, such as Canada, a load restriction factor shall be used — See Guide BXUV or BXUV7

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

    1. Flooring System — The flooring system shall consist of one of the following:

    System No. 1

      Subflooring — Min 15/32 thick plywood, min grade "C-D" or "Sheathing." Face grain of plywood or strength of axis of panel to be perpendicular to joists with joints staggered.
      Vapor Barrier — Optional - Nom 0.010 in. thick commercial rosin-sized building paper.
      Finish Flooring — Min 1 by 4 in. T&G lumber installed perpendicular to joists, or min 19/32 thick wood structural panels, min grade "Underlayment" or "Single-Floor." Face grain of plywood or strength of axis of panels to be perpendicular to joists with joints staggered.

      System No. 2

      Subflooring — Min 15/32 thick plywood, min grade "C-D" or "Sheathing." Face grain of plywood or strength of axis of panel to be perpendicular to joists with joints staggered.
      Vapor Barrier — (Optional) — Nom 0.030 in. thick commercial asphalt saturated felt.
      Finish Flooring - Floor Topping Mixture* — Min 3/4 or 1 in. thickness of floor topping mixture for 19/32 or 15/32 in. thick wood structural panels respectively, having a min compressive strength of 1000 psi. Refer to manufacturer's instructions accompanying the material for specific mix design.

      ALLIED CUSTOM GYPSUM — AccuCrete types NexGen, Green, Prime, B, M, and PrePour, AccuRadiant, AccuLevel types G40, G50 and SD30.


      Floor Mat Material* — (Optional) - Floor mat material nominal 2 - 9.5 mm thick loose laid over the subfloor. Floor topping shall be a min of 3/4 in. or 1 in. thick for 19/32 or 15/32 in. thick wood structural panels respecitively.

      ALLIED CUSTOM GYPSUM — AccuQuiet types P80, C40, D13, D-18, D25, DX38, EM.125, EM.125S, EM.250, EM.250S, EM.375, EM.375S, EM.750, and EM.750S.


      System No. 3

      Subflooring — Min 15/32 thick plywood, min grade "C-D" or "Sheathing." Face grain of plywood or strength of axis of panel to be perpendicular to joists with joints staggered.
      Vapor Barrier - (Optional) — Commercial asphalt saturated felt, 0.030 in. thick.
      Floor Mat Materials* - (Optional) — Nom 3 mm thick floor mat material adhered to subfloor with Hacker Floor Primer. Primer to be applied to the surface of the mat prior to the placement of floor-topping mixture. When floor mat material is used, min thickness of floor topping mixture is 3/4 in.. (19 mm)

      ECORE INTERNATIONAL INC — Type QTscu 4002


      HACKER INDUSTRIES INC — Type Hacker Sound-Mat


      Alternate Floor Mat Materials* — (Optional) — Floor mat material nom 1/4 in. (6 mm) thick adhered to subfloor with Hacker Floor Primer. Primer to be applied to the surface of the mat prior to the placement of a min 1-1/4 in. (32 mm) of floor-topping mixture.

      ECORE INTERNATIONAL INC — Type QTrbm 3006-3


      HACKER INDUSTRIES INC — Type Hacker Sound-Mat II


      Alternate Floor Mat Materials — (Optional) Floor Mat material Nom. 1/8" (3 mm) loose laid over the subfloor. Floor topping thickness shall be a minimum of 3/4 in.(19 mm)

      HACKER INDUSTRIES INC — FIRM-FILL SCM-125


      Alternate Floor Mat Materials* — (Optional) — Floor mat material nom 1/4 in. thick loose laid over the subfloor. Floor topping thickness shall be a min of 1 in.

      HACKER INDUSTRIES INC — Type FIRM-FILL SCM-250,


      Alternate Floor Mat Materials* — (Optional) — Floor mat material nom 3/8 in. thick loose laid over the subfloor. Floor topping thickness shall be a min of 1-1/4 in.

      HACKER INDUSTRIES INC — Type FIRM-FILL SCM-400,


      Alternate Floor Mat Materials* — (Optional) — Floor mat material nom 3/4 in. thick loose laid over the subfloor. Floor topping thickness shall be a min of 1-1/2 in.

      HACKER INDUSTRIES INC — Type FIRM-FILL SCM-750,


      Metal Lath (Optional) — For use with 3/8 in. or 10 mm floor mat materials, 3/8 in. expanded steel diamond mesh, 3.4 lbs/sq yd placed over the floor mat material. Hacker Floor Primer to be applied prior to the placement of the metal lath. When metal lath is used, floor topping thickness a nom 1-1/4 in. over the floor mat.
      Finish Flooring - Floor Topping Mixture* — — Min 3/4 in. thickness of floor topping mixture having a min compressive strength of 1100 psi. Mixture shall consist of 6.8 gal of water to 80 lbs of floor topping mixture to 1.9 cu ft of sand.


      HACKER INDUSTRIES INC — Types Firm-Fill Gypsum Concrete, Firm- Fill 2010, Firm-Fill 3310, Firm-Fill 4010, Firm-Fill High Strength, Gyp-Span Radiant, Gyp-Span High Strength


      System No. 4

      Subflooring — — Min 15/32 thick plywood, min grade "C-D" or "Sheathing." Face grain of plywood or strength of axis of panel to be perpendicular to joists with joints staggered.


      Vapor Barrier — — (Optional) - Commercial asphalt saturated felt, 0.030 in. thick.


      Vapor Barrier — — (Optional) - Nom 0.010 in. thick commercial rosin-sized building paper.


      Finish Flooring* — — Min 3/4 in. thickness of any Floor Topping Mixture bearing the UL Classification Marking as to Fire Resistance. See Floor- and Roof-Topping Mixtures (CCOX) category for names of Classified Companies.


      Floor Mat Materials* — — (Optional) - Nom. 1/4 in. thick loose laid over the subfloor. Floor topping thickness shall be a minimum of 3/4 in.


      KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 55/025 and Quiet Qurl 55/025 N


      Alternate Floor Mat Materials* — — (Optional) - Floor mat material Nom. 3/8 in. thick loose laid over the subfloor. Floor topping thickness shall be a minimum of 1 in.


      KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 60/040 and Quiet Qurl 60/040 N


      Alternate Floor Mat Materials* — (Optional) - Floor mat material Nom. 3/4 in. thick loose laid over the subfloor. Floor topping thickness shall be a minimum of 1-1/2 in.

      KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 65/075, Quiet Qurl 65/075 N


      Alternate Floor Mat Materials* — (Optional) - Floor mat material Nom. 1/4 in. entangled net core with a compressible fabric attached to the bottom loose laid over the subfloor. Floor topping thickness shall be a minimum of 1 in.

      KEENE BUILDING PRODUCTS CO INC — Quiet Qurl 55/025 MT and Quiet Qurl 55/025 N MT


      System No. 5

      Subflooring — Min 15/32 thick plywood, min grade "C-D" or "Sheathing." Face grain of plywood or strength of axis of panel to be perpendicular to joists with joints staggered.
      Vapor Barrier - (Optional) — Nom 0.030 in thick commercial asphalt saturated felt.
      Finish Flooring - Floor Topping Mixture* — Min 3/4 in. thickness of floor topping mixture having a minimum compressive strength of 1500 psi. Refer to manufacturer's instructions accompanying the material for specific mix design.

      MAXXON CORP — Types D-C, GC, GC 2000, L-R, T-F, CT, SS


      RAPID FLOOR SYSTEMS — Type RF, RFP, RFU, RFR, Ortecrete


      Floor Mat Materials* - (Optional) — Floor mat material loose laid over the subfloor. Refer to manufacturer's instructions regarding the minimum thickness of floor topping over each floor mat material.

      MAXXON CORP — Type Acousti-Mat I, Acousti-Mat II, Acousti-Mat II HP, Enkasonic 9110, Enkasonic 9110 HP, Acousti-Mat 3, Acousti-Mat 3 HP, Acousti-Mat LP, Acousti-Mat LP-R, Acousti-Mat SD.


      Floor Mat Reinforcement — — (Optional) - Refer to manufacturer's instructions regarding minimum thickness of floor topping over each floor mat material, primers, and use of crack suppression reinforcement.


      MAXXON CORP — Crack Suppression Mat (CSM) or Maxxon Reinforcement (MR)


      Metal Lath (For use with or as an alternate to Crack Suppression Mat (CSM) or Maxxon Reinforcement (MR)) — — 3/8 in. expanded galvanized steel diamond mesh, 3.4 lbs/sq yd loose laid over the floor mat material. Floor topping thickness shall be min 1-1/2 in.


      System No. 6

      Subflooring — Min 15/32 thick plywood, min grade "C-D" or "Sheathing." Face grain of plywood or strength of axis of panel to be perpendicular to joists with joints staggered.
      Vapor Barrier — (Optional) Nom 0.030 in. thick commercial asphalt saturated felt.
      Finish Flooring - Floor Topping Mixture* — Min 3/4 or 1 in. thickness of floor topping mixture for 19/32 or 15/32 in. thick wood structural panels respectively, having a min compressive strength of 1000 psi. Refer to manufacturer's instructions accompanying the material for specific mix design.

      FORMULATED MATERIALS LLC — Types FR-25, FR-30, and SiteMix.


      Floor Mat Material* — (Optional) Floor mat material nominal 2 - 9.5 mm thick loose laid over the subfloor. Floor topping shall be a min of 3/4 in. or 1 in. thick for 19/32 or 15/32 in. thick wood structural panels respectively.

      FORMULATED MATERIALS LLC — Types M1, M2, M3, R1, and R2


    System No. 7

    Subflooring — Min 15/32 thick plywood, min grade "C-D" or "Sheathing." Face grain of plywood or strength of axis of panel to be perpendicular to joists with joints staggered.
    Finish Flooring* — Floor Topping Materials — Min 3/4 in. to 1-1/2 in. thickness of any Floor Topping Mixture bearing the UL Classification Marking as to Fire Resistance with a minimum compressive strength of 1500 psi.

      See Floor- and Roof-Topping Mixtures (CCOX) category for names of Classified Companies.

    Floor Mat Materials* — (Optional) — Floor mat material nom 1/8 in. to 3/4 in. thick. Loose laid over the subfloor. When used, Acousti-flor CSM (crack suppression mat) is loose laid over the floor mat material. Floor topping material thickness is dependent on thickness of floor mat used.

    WALFLOR INDUSTRIES INC — Type Acousti-flor, Acousti-flor CSM. Floor topping thickness depends on products used as follows:


    Acousti-flor (1/8 in. thick) - Floor topping thickness shall be a minimum of 3/4 in.

    Acousti-flor (1/4 in. thick) - Floor topping thickness shall be a minimum of 1 in.

    Acousti-flor (3/8 in. thick) - Floor topping thickness shall be a minimum of 1 in.

    Acousti-flor (3/4 in. thick) - Floor topping thickness shall be a minimum of 1-1/2 in.

    Metal Lath — (Optional) — Expanded steel diamond mesh, 2.5 lb / sq yd loose laid over floor mat material.
    Fiberglass Mesh Reinforcement — (Optional) — Coated non-woven glass fiber mesh grid loose laid over floor mat material.
    2. Wood Joists — 2 by 10 in. spaced 16 in. OC.
    3. Cross Bracing — Min 1 by 3 in. or min 2 by 10 solid blocking.
    4. Batts and Blankets* — (Optional) - Glass fiber or mineral wool insulation bearing the UL Classification Marking as to Surface Burning Characteristics and/or Fire Resistance. Insulation shall be a max of 3-1/2 in. thick and shall be secured against the underside of the subflooring with staples spaced 12 in. OC.
    4A. Loose Fill Material* — (Optional) - As an alternate to Item 4 — For use with resilient channels only, not for use when gypsum board is directly attached to joists. Max 3-1/2 in. thickness of loose fill material bearing the UL Classification Marking for Surface Burning Characteristics, fitted in the concealed space, draped over the resilient channel/gypsum board ceiling membrane when resilient channel attachment is modified as specified in Item 5. The finished rating when loose fill material is used has not been determined.
    5. Resilient Channels — (Optional) - Formed from min 25 MSG galv steel spaced max 24 in. OC perpendicular to joists. When Loose Fill Material* is used, channels spaced a maximum 12 in. OC. Channels secured to each joist with min. 1-1/4 in. long, No. 8 steel screws. Channel ends butted and centered under the joists and attached to the joists with one screw at each end. Additional resilient channels positioned so as to coincide with end joints of gypsum board as shown in the above illustration. Additional channels shall extend min 3 in. beyond each side edge of board.
    5A. Framing Members* — (Optional) - Used as an alternate method to attach resilient channels to joists (Item 2). A resilient sound isolation accessory to be used at each intersection of the channels and joists. Channel ends butted and centered under the joists and attached to the joists with one accessory at each end. Additional accessories used to hold resilient channels that support the gypsum board end joints, as described in Item 5. The accessory envelops the mounting edge of the resilient channel. The accessory and resilient channel are fastened to the joists with the screws supplied with the resilient sound isolation accessory.

    ACOUSTIC PROPERTIES L L C — Type RC-1 Boost.


    6. Gypsum Board* — (For use with resilient channels) - Nom 5/8 in. thick, 48 in. wide gypsum board. Gypsum board installed with long dimension perpendicular to resilient channels and side edges located between joists. Secured with 1 in. bugle head, high-low thread steel screws spaced max 8 in. OC. End joints of gypsum board similarly fastened to additional resilient channels positioned at end joint locations. Screws shall be spaced 2 in. from end joints and 1 in. from side joints. Adjacent end joints staggered min 24 in.

    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM — Type C.


    6A. Gypsum Board* — (As an alternate to Item 6) - (For use with resilient channels) - Nom 3/4 in. thick, 48 in. wide gypsum board. Gypsum board installed with long dimension perpendicular to resilient channels and side edges located between joists. Secured with 1-1/8 in. bugle head, high-low thread steel screws spaced max 8 in. OC. End joints of gypsum board similarly fastened to additional resilient channels positioned at end joint locations. Screws shall be spaced 2 in. from end joints and 1 in. from side joints. Adjacent end joints staggered min 24 in.

    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM — Type PG-13.


    6B. Gypsum Board* — (For use when directly attached to joists) -Not Shown -- Nom 5/8 in. thick, 48 in. wide gypsum board, installed with long dimension perpendicular to joists. Gypsum board secured with 1-7/8 in. long, 6d cement coated nails spaced 6 in. OC.

    PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM — Type C.


    7. Finishing System (Not Shown) — Paper tape embedded in joint compound over joints and covered with 2 layers of compound with edges feathered out. Gypsum board screw heads covered with 2 layers of compound.

    * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively.

Last Updated on 2017-11-17
BXUV.M519 M519 BXUV 100046076 DESIGN Active 20171117 20171117 P794913 P794913 100239807 130869004 100239807 130869004 130869004 130869004 130869004 130869004 130869004 100057537 100057537 100057537 100057537 720780001 131207001 720780001 720780001 P1751555 P1751555 100607356 P994182 100046076 100046076 100046076

Design/System/Construction/Assembly Usage Disclaimer

  • Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL Certified products, equipment, system, devices, and materials.
  • Authorities Having Jurisdiction should be consulted before construction.
  • Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with applicable requirements. The published information cannot always address every construction nuance encountered in the field.
  • When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate methods of construction.
  • Only products which bear UL's Mark are considered Certified.

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "© 2017 UL LLC".